InRow® RPChilled Water/Direct Expansion — 50/60 HzTechnical DataAIR-COOLEDACRP100ACRP101ACRP102CHILLED WATERACRP500ACRP501ACRP502
InRow RP Technical Data Manual6Optional FeaturesCable Water DetectorA leak detection cable is placed on the floor or subfloor around all possible leak
7InRow RP Technical Data ManualMicroprocessor ControllerMicroprocessor Controller The microprocessor controller is standard on each system. The contro
InRow RP Technical Data Manual8AlarmsThe microprocessor controller shall activate a visible and audible alarm in the following occurrences:• Cool Fai
9InRow RP Technical Data ManualInRow RP ModelsHinged rear doorsCasters (all swiveling)Side panel lockDoor handle and lockRemovable side panelDis
InRow RP Technical Data Manual10Chilled Water Interior Components (front of unit)Electric heater (for reheat)Electrical panelFanSupply temperature
11InRow RP Technical Data ManualChilled Water Interior Components (back of unit)Chilled water coilRear doorsChilled water control actuatorAir filt
InRow RP Technical Data Manual12Air-cooled Interior Components (front of unit)Electric heater (for reheat)Main circuit breakerCondensate drain pan
13InRow RP Technical Data ManualAir-cooled Interior Components (back of unit)Evaporator coilShutoff valves (top piping only)Condensate drain panAi
InRow RP Technical Data Manual14Chilled Water and Air-cooled User Interface ConnectionsRack inlet temperature sensors 1, 2, 3A-Link INA-Link OUTNe
15InRow RP Technical Data ManualChilled Water Electrical PanelNote: ACRP501 shown. Transformers User interface connectors Main controller board Re
American Power Conversion Legal DisclaimerThe information presented in this manual is not warranted by the American Power Conversion Corporation to be
InRow RP Technical Data Manual16Air-cooled Electrical PanelNote: ACRP 101 shown. Transformers User interface connectors Main controller board Rela
17InRow RP Technical Data ManualPerformance SpecificationsChilled Water Performance Specifications 5.5°C (42°F) EWTTemperature dry bulb (DB), wet bulb
InRow RP Technical Data Manual18Chilled Water Performance Specifications 7.2°C (45°F) EWTTemperature dry bulb (DB), wet bulb (WB)°C (°F)CW Delta T°C (
19InRow RP Technical Data ManualChilled Water Performance Specifications 8.9°C (48°F) EWT (Temperature dry bulb (DB), wet bulb (WB)°C (°F)CW Delta T°C
InRow RP Technical Data Manual20Chilled Water Performance Specifications 10°C (50°F) EWTTemperature dry bulb (DB), wet bulb (WB)°C (°F)CW Delta T°C (°
21InRow RP Technical Data ManualChilled Water Performance Specifications 12.8°C (55°F) EWTTemperature dry bulb (DB), wet bulb (WB)°C (°F)CW Delta T°C
InRow RP Technical Data Manual22Chilled Water Performance Specifications 15.5°C (60°F) EWTTemperature dry bulb (DB), wet bulb (WB)°C (°F)CW Delta T°C
23InRow RP Technical Data ManualChilled Water Data - GeneralMODEL ACRP 500 SeriesMODULATING VALVESSize -3 Way Ball Valve - NPT mm (in) 25.4 (1)AIR SYS
InRow RP Technical Data Manual24Glycol Correction FactorsAltitude Correction Factors for InRow ProductsAir-cooled Performance SpecificationsPerformanc
25InRow RP Technical Data ManualAir-cooled Data - GeneralNote: Reduce airflow and cooling capacity specifications by 7% for cooling units run at low i
ContentsInRow RP Technical Data ManualiOverview ... 1Capacity . . . . . . . .
InRow RP Technical Data Manual26Sound Performance DataElectrical DataChilled Water Tested Sound DataFan Speed% Airflow m3/s (SCFM)Sound Power dB at F
27InRow RP Technical Data ManualDimensional DataInRow RP Assembled ModuleDimensions are shown in mm (in).na2465a
InRow RP Technical Data Manual28SX to VX Height AdapterSX to 48U SX Height AdapterDimensions are shown in mm (in).na2445ana2446a
29InRow RP Technical Data ManualPiping and Mechanical ConnectionsChilled Water Piping DiagramFlex hose or copper Circuit setter (field-installed)Coppe
InRow RP Technical Data Manual30Top Chilled Water Piping Access (top view)Note: Top or bottom entry can be chosen individually for each type of connec
31InRow RP Technical Data ManualBottom Chilled Water Piping Access (bottom view, looking up)Dimensions are shown in mm (in).Water supply to chillerW
InRow RP Technical Data Manual32Air-cooled Piping DiagramNote: Shutoff valves shown nearest to the condensers are not supplied by APC.Note: Route pipi
33InRow RP Technical Data ManualAir-cooled Piping Access (top)Dimensions are shown in mm (in). Refrigerant discharge line Refrigerant liquid line P
InRow RP Technical Data Manual34Air-cooled Piping Access (bottom view, looking up)Dimensions are shown in mm (in).Pressure relief valve access—27.80
35InRow RP Technical Data ManualAir-Cooled CondensersMechanical DataSKUAmbient TempSound Pressure (dbA)*Sound Pressure (dbA) **Air Quantity Fan Unit C
InRow RP Technical Data ManualiiInRow RP Models ... 9Chilled Water Interior Components (front
InRow RP Technical Data Manual36ACCD75201 and ACCD75204ACCD75202 and ACCD75205ACCD75203 and ACCD75206Dimensions are shown in mm (in).Note: All condens
37InRow RP Technical Data ManualACCD75207ACCD75208 and ACCD75209Dimensions are shown in mm (in). All condensers shown on this page have 16 m
InRow RP Technical Data Manual38Guide SpecificationsPART 1 — GENERAL1.01 SUMMARYA. The environmental control system shall be designed specifically for
39InRow RP Technical Data ManualB. VARIABLE SPEED FAN ASSEMBLY1. Variable Speed Fans: The unit is equipped with variable speed, electronically commuta
InRow RP Technical Data Manual40k. Fan faultl. Fan run hours exceededm. Water detection faultn. Condensate pump faulto. Condensate run hours exceededp
41InRow RP Technical Data Manualba. Air flow decreased while compressor offbb. Suction pressure sensor failurebc. Discharge pressure sensor failurebd.
InRow RP Technical Data Manual42J. CONDENSATE PUMPFactory installed and wired condensate pump shall pump at 31.99 l/h (8.45 GPH) at 3.5 m (11.5 ft) of
43InRow RP Technical Data ManualP. SELECTABLE TOP OR BOTTOM PIPING (AIR-COOLED ONLY)1. Pipe connections: The unit is equipped with field connection fr
InRow RP Technical Data Manual44Guidelines for InstallationThe InRow RP provides reliable, accurate temperature control of computer rooms, laboratorie
1InRow RP Technical Data ManualOverviewThe modular, row-based computer room cooling system offers efficient, predictable, and economical cooling for a
9/2009990-2469E-001APC Worldwide Customer SupportCustomer support for this or any other APC product is available at no charge in any of the following
InRow RP Technical Data Manual2Scalable Solution for Critical EnvironmentsInRow AdvantagesThe row-based solution improves energy efficiency and coolin
3InRow RP Technical Data ManualHot Aisle Containment System Modular ceiling tiles and doors can be used to enclose the hot aisle. This increases the d
InRow RP Technical Data Manual4Standard FeaturesInsulated CabinetThe frame is constructed of 1.5 mm (16 gauge) formed steel for maximum strength. Cabi
5InRow RP Technical Data ManualDual Position Float Condensate ManagementThe pump is factory wired and piped internally to the condensate drain pan and