APC 208 VAC Bedienungsanleitung Seite 4

  • Herunterladen
  • Zu meinen Handbüchern hinzufügen
  • Drucken
  • Seite
    / 10
  • Inhaltsverzeichnis
  • LESEZEICHEN
  • Bewertet. / 5. Basierend auf Kundenbewertungen
Seitenansicht 3
Output
Output Power Capacity 2250 Watts / 3000 VA
Max Configurable Power 2250 Watts / 3000 VA
Nominal Output Voltage 120V,208V
Efficiency at Full Load 93%
Output Voltage Distortion Less than 5% at full load
Output Frequency (sync to mains) 57 - 63 Hz for 60 Hz nominal
Crest Factor up to 5 : 1
Waveform Type Sine wave
Output Connections
(6) NEMA 5-15R
(1) NEMA L14-30R
(2) NEMA L6-30R
Bypass Internal Bypass (Automatic and Manual)
Input
Nominal Input Voltage 208V
Input Frequency 60 Hz +/- 5 Hz
Input Connections
NEMA L6-30P
Cord Length 1.83 meters
Input voltage range for main
operations
156 - 252 (208) / 176 - 282 ( 240V)V
Other Input Voltages 240
Batteries & Runtime
Battery Type Maintenance-free sealed Lead-Acid battery with suspended electrolyte : leakproof
Typical recharge time 3.50 hour(s)
Replacement Battery RBC14
Replacement battery cartridge note RBC14 is the RBC for a SmartCell-XR. There is no RBC available for a standard
SmartCell. If an RBC is needed for a standard SmartCell,then an entire SmartCell
will need to be purchased. Due to the weight of RBC14 APC does not offer pre-paid
return postage for this RBC.
Typical Backup Time 111.8 minutes (1125 Watts)
Seitenansicht 3
1 2 3 4 5 6 7 8 9 10

Kommentare zu diesen Handbüchern