Smart-UPS Rack-Mount2U 750/1000/1500 VA 120/230 Vac, 3000 VA 100/120/208/230 Vac, 2200 VA 120 Vac 12
Customize the Main and Controlled Outlet Groups
Use the Control menus to change the Main Outlet Group and the Controlled Outlet Group settings.
Network Management Card Settings
These settings are available only on units that have a Network Management Card (NMC) and are set in the factory.
These settings can only be modified using an external interface, like the NMC web interface.
NMC IP Address Mode
NMC IP Address
NMC Subnet Mask
NMC Default Gateway
Function Factory Default Options Description
Name String
Outlet Group
Outlet Group 1
Edit these names using an external interface, such as the Network
Management Card Web interface.
UPS Name String UPS Outlets
Turn On Delay 0 sec
Set the value in
seconds
The amount of time the UPS or
the Controlled Outlet
Group
will wait between receiving the command to turn
on and the actual startup.
Turn Off Delay
• 0 sec (UPS Outlets)
• 90 sec (Controlled
Outlet Groups)
Set the value in
seconds
The amount of time that the UPS or
the Controlled
Outlet Group
will wait between receiving the command
to turn off and the actual shut down.
Reboot Duration 8 sec
Set the value in
seconds
The amount of time that the UPS or
the Controlled
Outlet Group
must remain off before it will restart.
Minimum Return
Time
0 sec
Set the value in
seconds
The amount of battery runtime that must be available
before the UPS or
the Controlled Outlet Group will turn
on.
Load Shed On
Battery
Disabled
• Shutdown with
Delay
• Shutdown
immediately
• Turn off
immediately
• Turn off with delay
• Disabled
When the unit switches to battery power, the UPS can
disconnect power to the
Controlled Outlet Group to save
runtime.
Configure this delay time, use the
LOAD SHED TIME
WHEN ON BATTERY setting.
Load Shed Time
when On Battery
Disabled
Set the value in
seconds
The amount of time the outlets will function on battery
power before they will turn off.
Load Shed On
Runtime
Disabled
• Shutdown with
delay
• Shutdown
immediately
• Turn off
immediately
• Turn off with delay
• Disabled
When the battery runtime falls below the specified
value, the
Controlled Outlet Group will turn off.
Configure this time using the
LOAD SHED RUNTIME
REMAINING setting.
Load Shed On
Runtime
Remaining
Disabled
Set the value in
seconds
When the remaining runtime reaches this level, the
Controlled Outlet Group will turn off.
Load Shed on
Overload
Disabled
• Disabled
• Enabled
In the event of an overload (greater than 100% output),
the
Controlled Outlet Group will immediately turn off to
conserve power for critical loads. The
ControlledOutlet
Group
will only turn on again with a manual command.
Seitenansicht 12