®—0 HzAir-Cooled/Fluid-Cooled 50/6Technical DataACRD100, ACRD101,ACRD200, ACRD201ACRD500, ACRD501,ACRD502
InRow RD Technical Data Manual2Scalable Solution for Critical EnvironmentsInRow AdvantagesThe row-based solution improves energy efficiency and coolin
3InRow RD Technical Data ManualHot Aisle Containment System Modular ceiling tiles and doors can be used to enclose the hot aisle. This increases the d
InRow RD Technical Data Manual4Standard FeaturesCabinetThe frame is constructed of 16 gauge formed steel for maximum strength. The cabinet is servicea
5InRow RD Technical Data ManualNetwork Management CardThe Network Management Card (NMC) allows communication with the Local Area Network (LAN). In add
InRow RD Technical Data Manual6Optional FeaturesCable Water DetectorA leak detection cable is placed on the floor or subfloor around all possi-ble lea
7InRow RD Technical Data ManualMicroprocessor ControllerMicroprocessor Controller The microprocessor controller is standard on each unit. The controll
InRow RD Technical Data Manual8AlarmsThe microprocessor controller shall activate a visible and audible alarm in the following occurrences:All series:
9InRow RD Technical Data ManualInRow RD ModelsExterior components: ACRD100 and ACRD200 seriesRemovable rear doorAdjustable leveling feetSide panel
InRow RD Technical Data Manual10Interior components (front): ACRD100 seriesElectrical control box 1 (retractable)CompressorElectrical control box 2
11InRow RD Technical Data ManualInterior components (rear): ACRD100 seriesFilter/dryerHot gas bypass valvePressure transducer (2 total, located beh
American Power Conversion Legal DisclaimerThe information presented in this manual is not warranted by the American Power Conversion Corporation to be
InRow RD Technical Data Manual12Interior components (front): ACRD200 seriesElectrical control box 1 (retractable)CompressorElectrical control box 2
13InRow RD Technical Data ManualInterior components (rear): ACRD200 seriesFilter/dryerElectrical control box 2Pressure transducer (2 total, located
InRow RD Technical Data Manual14Exterior components: ACRD500 seriesRemovable rear doorsCasters (all swiveling)Side panel lockDoor handle and lock
15InRow RD Technical Data ManualInterior components (front): ACRD500 seriesCondensate drain panFan (2)Thermal expansion valveFan guard (2)Compres
InRow RD Technical Data Manual16Interior components (rear): ACRD500 seriesEvaporator coilShutoff valvesCondensate drain panAir filtersSight glass
17InRow RD Technical Data ManualElectrical panel: ACRD100 and ACRD200 seriesLeak detector portBuilding management system (BMS) RS-485 portRemote te
InRow RD Technical Data Manual18Electrical panel: ACRD500 seriesTransformersUser interface connectorsMain controller boardRelay boardGround lugM
19InRow RD Technical Data ManualUser interface panel: ACRD500 seriesRack inlet temperature sensors 1, 2, 3A-Link INA-Link OUTNetwork portConsole
InRow RD Technical Data Manual20Performance SpecificationsNet Cooling Capacity (Air and Glycol Cooled)Return Air Temperature SKU Total Capacity kW (BT
21InRow RD Technical Data ManualNet Cooling Capacity (Water Cooled)Return Air Temperature SKU Total Capacity kW (BTU/hr) Sensible Capacity kW (BTU/hr)
InRow RD Technical Data Manual22Performance at Percentage of Fan SpeedACRD100 Series% Fan SpeedVoltage/Phase/HzL/S (SCFM)Unit Power in kWCondenser Fan
23InRow RD Technical Data ManualACRD200 Series% Fan SpeedVoltage/Phase/Hz L/S (SCFM)Unit Power in kWNet Sensible Capacity kW (BTU/h)SA Temp °C (°F)Ret
InRow RD Technical Data Manual24ACRD500 Series% Fan Speed Voltage L/S (SCFM)Unit Power in kWCondenser Fan Power in kWNet Sensible Capacity kW (BTU/h)S
25InRow RD Technical Data ManualGeneral DataGeneral Specifications - ACRD200 SeriesData Units Water Cooled Glycol Mixture CooledNominal flow rate ente
InRow RD Technical Data Manual26Air-CooledData SKU ValueAIR SYSTEM - FAN (Standard Filter Installed)Size - mm (in)ACRD100 200 (7.9)ACRD101 200 (7.9)AC
27InRow RD Technical Data ManualAltitude Correction FactorsRoom Condition: 72 DB/50% RHAltitude (ft)0 1000 2000 3000 4000 5000 6000 7000 8000 9000 100
InRow RD Technical Data Manual28 Electrical DataSKU MCA MOP FLACompressorPowerLRA RLAACRD100208-240V, 60Hz25 40 N/A 87.5 16.0 4.6ACRD101220-240V, 50Hz
29InRow RD Technical Data ManualDimensional DataACRD100 and ACRD200 seriesDimensions are shown in mm (in).na2231b
InRow RD Technical Data Manual30ACRD500 seriesDimensions are shown in mm (in).na2465a
31InRow RD Technical Data ManualNetShelter SX to VX Height Adapter: ACRD100 and ACRD200 seriesNetShelter SX to VX Height Adapter: ACRD500 seriesNetShe
InRow RD Technical Data Manual32Piping and Mechanical ConnectionsRefrigeration Piping Diagram (ACRD100 and ACRD500 series)Note: Shutoff valves shown n
33InRow RD Technical Data ManualWater cooled piping (ACRD200 series)Note: Bottom piping shown.InRow RDGate valve*Strainer, 20 mesh*Hose bib** Fie
InRow RD Technical Data Manual34Glycol cooled piping (ACRD200 series)Note: Bottom piping shown.Expansion tank*Hose bibs*Tank fill*Gate valves*Flu
35InRow RD Technical Data ManualTop piping and power access locations (ACRD100 series and ACRD200 series)Dimensions are shown in mm (in).Low voltage
InRow RD Technical Data Manual36Bottom piping and power access locations (ACRD100 series and ACRD200 series)Dimensions are shown in mm (in).Electrica
37InRow RD Technical Data ManualTop piping and power access locations (ACRD500 series)Dimensions are shown in mm (in).Refrigerant discharge lineRefr
InRow RD Technical Data Manual38Bottom piping and power access locations (ACRD500 series)Dimensions are shown in mm (in).Refrigerant liquid lineRefr
39InRow RD Technical Data ManualOutdoor Heat ExchangersAir Cooled Condensers - Mechanical Data (ACRD100 Series)SKUAmbient Tem p°C (°F)Sound Pressure (
InRow RD Technical Data Manual40Air Cooled Condensers - Electrical Data (ACRD100 Series)SKU Voltage Phase Frequency FLA MCA MOPACCD75214 208-240V 1 ph
41InRow RD Technical Data ManualACCD75201 and ACCD75204ACCD75202 and ACCD75205ACCD75203 and ACCD75206Dimensions are shown in mm (in). All co
ContentsInRow RD Technical Data ManualiOverview ... 1Scalable Solution for Crit
InRow RD Technical Data Manual42ACCD75207ACCD75208 and ACCD75209Dimensions are shown in mm (in). All condensers shown on this page have 16 m
43InRow RD Technical Data ManualACCD75214ACCD75215ACCD75216 and ACCD75218Dimensions are shown in mm (in).na2891ana2895ana2893a
InRow RD Technical Data Manual44ACCD75217 and ACCD75219ACFC75210ACFC75255Dimensions are shown in mm (in).na2896ana2890ana2899a
45InRow RD Technical Data ManualACFC75256Dimensions are shown in mm (in).ACFC75257Dimensions are shown in mm (in).Air-cooled Condenser FeaturesAvailab
InRow RD Technical Data Manual46Guide SpecificationsPART 1 — GENERAL1.01 SUMMARYA. The environmental control system shall be designed specifically for
47InRow RD Technical Data ManualPART 2 — PRODUCT2.01 STANDARD COMPONENTSA. Cabinet Construction1. Front and rear exterior panels shall be 18 gauge per
InRow RD Technical Data Manual48C. Main Disconnect Switch1. The unit shall be provided with thermal-magnetic circuit breakers with interrupt capacity
49InRow RD Technical Data Manualu. Internal communication faultv. On standby input contact faultw. A-link isolation relay faultx. Excessive compressor
InRow RD Technical Data Manual50F. Cooling Coil And Condensate Pan1. ACRD100 and ACRD200 series:a. The cooling coil shall use corrugated aluminum fin
51InRow RD Technical Data ManualI. Filters1. ACRD100 series and ACRD200 series:a. The standard filters shall be 20% efficient per ASHRAE 52.1, MERV 1
InRow RD Technical Data ManualiiInRow RD Models ... 9Exterior components: ACRD100 and ACRD200
InRow RD Technical Data Manual52N. Bridge Data Partition1. An overhead cable distribution, that sits between adjacent NetShelter racks and allows for
53InRow RD Technical Data ManualGuidelines for InstallationThe InRow RD provides reliable, accurate temperature control of computer rooms, laboratorie
InRow RD Technical Data Manual54Condensate drainCondensation from the evaporator pan is collected and discharged by the condensate pump to a condensat
09/2008990-3236B-001*990-3236B-001*APC Worldwide Customer SupportCustomer support for this or any other APC product is available at no charge in any o
InRow RD Technical Data ManualiiiPiping and Mechanical Connections ...32Refrigeration Piping Diagram (ACRD100 and ACRD500 seri
InRow RD Technical Data ManualivSKU Selection Width Voltage Plug TypeACRD100 300 mm208-240V60 Hz 1 phHard wiredACRD101 300 mm220–240V50 Hz 1 phHard wi
1InRow RD Technical Data ManualOverviewThe modular, row-based computer room cooling system offers efficient, predictable, and economical cooling for a