Page 11 10/05/09
c. Sufficient APC CAN bus PCB’s to provide adequate communications of the PSMBC status
to the UPS system parallel control system.
3. The PSMBC shall be available as a line-up-and-match enclosure, circuit breaker, NEMA 1
enclosure.
4. The PSMBC shall carry a UL 1778 agency listing.
F. Software and Connectivity:
1. Network Adaptor: The ethernet web/SNMP adaptor shall allow one or more network
management systems (NMS) to monitor and manage the UPS in TCP/IP network
environments. The management information base (MIB) shall be provided in DOS and UNIX
"tar" formats. The SNMP interface adaptor shall be connected to the UPS via the RS-232
serial port on the standard communication interface board.
2. Unattended Shutdown: The UPS, in conjunction with a network interface card, shall be
capable of gracefully shutting down one or more operating systems during when the UPS is on
reserve mode. The UPS shall also be capable of using an RS-232 port to communicate by
means of serial communications to gracefully shut down one or more operating systems during
an on battery situation.
G. Remote UPS Monitoring: The following three methods of remote UPS monitoring shall be
available:
1. Web Monitoring: Remote monitoring shall be available via a web browser such as Internet
Explorer.
2. RS-232 Monitoring: Remote UPS monitoring shall be possible via either RS-232 or contact
closure signals from the UPS.
3. Simple Network Management Protocol (SNMP): Remote UPS monitoring shall be possible
through a standard MIB II compliant platform.
H. Software Compatibility: The UPS manufacturer shall have available software to support graceful
shutdown and or remote monitoring for the following systems:
1. Microsoft Windows 95/98/XP.
2. Microsoft Windows NT 4.0 SP6/2000.
3. OS/2.
4. Netware 3.2 – 5.1.
5. MAC OS 9.04, 9.22, 10.
6. Digital Unix/True 64.
7. SGI 6.0-6.5.
8. SCO UNIX.
9. SVR4 2.3, 2.41.
10. SCO Unix Ware 7.0 - 7.11.
11. SUN Solaris 2.6-2.8.
12. SUN OS 4.13, 4.14.
13. IBM AIX 4.3x-4.33g, 5.1.
14. HP-UX 9.x-11.i.
PART 3 - EXECUTION
3.1 EXAMINATION
A. Verification of Conditions: Examine areas and conditions under which the work is to be installed,
and notify the Contractor in writing, with a copy to the Owner and the Architect/Engineer, of any
conditions detrimental to the proper and timely completion of the work. Do not proceed with the
work until unsatisfactory conditions have been corrected.
1. Beginning of the work shall indicate acceptance of the areas and conditions as satisfactory by
the Installer.
3.2 INSTALLATION