APC 150kVA PDU W/ 480 PRI 208/120 SEC K1 XMER Spezifikationen

Stöbern Sie online oder laden Sie Spezifikationen nach Stromverteilungseinheiten (PDUs) APC 150kVA PDU W/ 480 PRI 208/120 SEC K1 XMER herunter. APC 150kVA PDU W/ 480 PRI 208/120 SEC K1 XMER Benutzerhandbuch

  • Herunterladen
  • Zu meinen Handbüchern hinzufügen
  • Drucken

Inhaltsverzeichnis

Seite 1 - Installation

Installationand Start-up150 kW InfraStruXure®Power Distribution Unit480 V / 600 V

Seite 2 - 동봉된 CD 안에 한국어 매뉴얼이 있습니다

2 150 kW InfraStruXure Power Distribution UnitWarningsReceiving/movingDo not tilt the PDU more than 45° from its vertical axis. Never lay the PDU on i

Seite 3 - About This Manual

Safety: Warnings150 kW InfraStruXure Power Distribution Unit 3Total power off procedure1. Open (turn OFF) the main input breaker on the PDU.2. Open (t

Seite 4

Safety: Warnings4 150 kW InfraStruXure Power Distribution UnitEMIThis equipment has been tested and found to comply with the limits for Class A digita

Seite 5 - Contents

150 kW InfraStruXure Power Distribution Unit 5Site PlanningDimensionsInfraStruXure PDUNetShelter VX enclosure81 in (2060 mm)7.2 in(183 mm)Without PDU

Seite 6

6 150 kW InfraStruXure Power Distribution UnitSpace ConsiderationsStudy the figure below to determine your space requirements for installing the Infra

Seite 7

150 kW InfraStruXure Power Distribution Unit 7Weight ConsiderationsEnsure that the floor and sub-floor can support the total weight of the configurati

Seite 8

8 150 kW InfraStruXure Power Distribution UnitHeat Output Consider the heat dissipation ratings of equipment to determine cooling requirements. Additi

Seite 9

150 kW InfraStruXure Power Distribution Unit 9Electrical Requirements and SpecificationsElectrical requirements† Provided by customer. Copper conducto

Seite 10 - Warnings

10 150 kW InfraStruXure Power Distribution UnitEmergency Power Off (EPO)OverviewTo provide a mechanism for applying emergency power off, attach a remo

Seite 11 - Emergency Power Off (EPO)

150 kW InfraStruXure Power Distribution Unit 11Basic Installation ProcedureThis section provides basic instructions for installing InfraStruXure power

Seite 12 - Safety: Warnings

This manual is available in English on the enclosed CD.Uživatelská pøíruèka v èeštinì je k dispozici na pøiloženém CD.Dieses Handbuch ist in Deutsch a

Seite 13 - Site Planning

Site Planning: Basic Installation Procedure12 150 kW InfraStruXure Power Distribution Unit7. Connect an EPO switch to the PDU monitoring unit.8. Insta

Seite 14 - Space Considerations

150 kW InfraStruXure Power Distribution Unit 13Installation ProceduresLevel the PDU and NetShelter EnclosuresLeveling feet are provided under each bot

Seite 15 - Weight Considerations

14 150 kW InfraStruXure Power Distribution UnitConnect the Power Source to the PDUAccess the PDU main input breakerOpen the back doors of the PDU by f

Seite 16 - Heat Output

Installation Procedures: Connect the Power Source to the PDU150 kW InfraStruXure Power Distribution Unit 15– For overhead wiring: Remove the gland pla

Seite 17 - Electrical requirements

Installation Procedures: Connect the Power Source to the PDU16 150 kW InfraStruXure Power Distribution UnitRoute the input conductors to the main inpu

Seite 18

150 kW InfraStruXure Power Distribution Unit 17Connect an Emergency Power Off SwitchOverviewConnecting the switch. The Emergency Power Off (EPO) switc

Seite 19 - See also

Installation Procedures: Connect an Emergency Power Off Switch18 150 kW InfraStruXure Power Distribution UnitConnect an EPO switch to the user connect

Seite 20

Installation Procedures: Connect an Emergency Power Off Switch150 kW InfraStruXure Power Distribution Unit 193. Test the EPO switch to ensure it is wi

Seite 21 - Installation Procedures

Installation Procedures: Connect an Emergency Power Off Switch20 150 kW InfraStruXure Power Distribution UnitSafety warningsHazardous voltage from the

Seite 22

150 kW InfraStruXure Power Distribution Unit 21Connect User Input Contacts and Relay Outputs to the User Connection PlateOverviewMake contact closure

Seite 23

150 kW InfraStruXure Power Distribution Unit iAbout This Manual This manual is intended for APC field service engineers or APC-trained installers of a

Seite 24 - Terminal Torque Tools

Installation Procedures: Connect User Input Contacts and Relay Outputs to the User Connection Plate22 150 kW InfraStruXure Power Distribution UnitTo c

Seite 25 - Overview

150 kW InfraStruXure Power Distribution Unit 23Install Shielding Troughs, Shielding Partitions, and Cable LaddersShielding troughs and shielding parti

Seite 26 - Normally ClosedNormally Open

Installation Procedures: Install Shielding Troughs, Shielding Partitions, and Cable Ladders24 150 kW InfraStruXure Power Distribution UnitShielding pa

Seite 27 - Active Alarm xxofxx

150 kW InfraStruXure Power Distribution Unit 25Install InfraStruXure Rack-Mount DevicesInstall the Rack Automatic Transfer Switches (ATSs)Install a ra

Seite 28 - Safety warnings

26 150 kW InfraStruXure Power Distribution UnitRoute and Attach Overhead WiringRoute and attach power cables to equipment racksIf you ordered overhead

Seite 29

Installation Procedures: Route and Attach Overhead Wiring150 kW InfraStruXure Power Distribution Unit 27– For dual-feed devices within a redundant sys

Seite 30

Installation Procedures: Route and Attach Overhead Wiring28 150 kW InfraStruXure Power Distribution Unit5. From each NetShelter VX enclosure, run the

Seite 31

150 kW InfraStruXure Power Distribution Unit 29Wiring Under the FloorIf routing power cables to enclosures under a raised floor, you must provide the

Seite 32

Installation Procedures: Wiring Under the Floor30 150 kW InfraStruXure Power Distribution Unit5. At the distribution panel, cut the power cable to the

Seite 33

150 kW InfraStruXure Power Distribution Unit 31Route Data Cables to the InfraStruXure Manager Hub (or Switch)1. Connect a CAT-5 network cable (provide

Seite 36

150 kW InfraStruXure Power Distribution Unit 33Start-Up ProcedureSafety warningsThis section provides instructions on how to perform a system start-up

Seite 37 - Wiring Under the Floor

Start-Up Procedure34 150 kW InfraStruXure Power Distribution Unit3. Open (turn OFF) the main output breaker on the front of the PDU. Apply power to th

Seite 38

Start-Up Procedure150 kW InfraStruXure Power Distribution Unit 354. Close (turn ON) the main output breaker on the front of the PDU. 5. Close (turn ON

Seite 39 - Manager Hub (or Switch)

Start-Up Procedure36 150 kW InfraStruXure Power Distribution Unit6. Close (turn ON) all sub-feed breakers (if applicable).

Seite 40

150 kW InfraStruXure Power Distribution Unit 37Configure the InfraStruXure ManagerOnce all equipment is installed, network cables have been connected

Seite 42 - Apply power to the system

150 kW InfraStruXure Power Distribution Unit 39Appendix A: OperationHow to Apply Power to the SystemThis procedure provides instruction for re-applyin

Seite 43

Appendix A: Operation40 150 kW InfraStruXure Power Distribution Unitb. Close (turn ON) the individual PDU distribution panel circuit breakers.c. Close

Seite 44

150 kW InfraStruXure Power Distribution Unit 41How to Ensure Total Power Off1. Open (turn OFF) the main circuit breaker for the power source feeding t

Seite 45

Contents150 kW InfraStruXure Power Distribution Unit iiiSafety ...1Overview . . . .

Seite 47 - Appendix A: Operation

Index 150 kW InfraStruXure Power Distribution Unit 43AApplying powe

Seite 48

44 150 kW InfraStruXure Power Distribution UnitUUpdates, to this manual iWWarnings 2–4Wiring, under the flo

Seite 52 - Wiring, under the floor 29

02/2008990-1983B*990-1983B*APC Worldwide Customer SupportCustomer support for this or any other APC product is available at no charge in any of the fo

Seite 53

iv 150 kW InfraStruXure Power Distribution UnitInstallation Procedures ... 13Level the PDU and NetShelter Enclo

Seite 54

150 kW InfraStruXure Power Distribution Unit vStart-Up Procedure ...33Safety warnings . . . . . . . .

Seite 56 - *990-1983B*

150 kW InfraStruXure Power Distribution Unit 1Safety OverviewSave these instructionsThis manual contains important instructions that must be followed