19InRow RD Operation and Maintenance
General Configuration
The cooling group configuration options are set during the commissioning of the cooling units in the
cooling group.
Caution: This procedure is to be performed by APC authorized personnel only. Changing
the settings incorrectly can cause malfunctions to your cooling unit.
Cooling unit configuration
Path: Main > Configure Unit > General
Capacity.
Set the cooling capacity of the cooling unit:
Auto: The cooling unit automatically controls its output under normal (default) conditions.
Max: The cooling unit runs at full capacity.
Note: Normal checks for cooling failures are disabled in the Max mode.
Start-up Dly. Enter a value for the delay. The start-up delay begins when the cooling unit is started and
initialized. The cooling unit cannot begin operation until this delay expires. Use the start-up delay to
restart equipment sequentially in your room after a scheduled downtime or a power outage.
Idle On Leak. When set to Yes , the cooling unit will enter idle mode if a Water Detection Fault
activates. Set to No to disable the cooling unit from entering idle mode if a leak is detected.
Note: The leak sensor (APC part number AP9325) is optional.
Note: There are three alarms that will cause the cooling unit to enter idle mode:
• Water Detection Fault (when Idle On Leak is set to Yes )
• Condensate Pump Fault
• Cooling Failure
See “Alarm messages and suggested actions” on page 32 for more information on alarms.