4
Metered Rack PDU
TheMeteredRackPDUprovidesreal-timeremotemonitoringofconnectedloads.
User-denedalarmswarnofpotentialcircuitoverloadsbeforecriticalITfailuresoccur.
•LocalandWeb-basedmonitoring
•ActivepowermeteringatPDUlevel
•User-denedalarmthresholds
•Widerangeofinputandoutputconnections
Step 2 (continued)
APC Item # Description Mounting Load Capacity Voltage Input Cord Length Output Connections
AP7830
RackPDU,Metered,ZeroU,20A,
120V,(24)NEMA5-20R
Vertical 1.9kW 120V NEMAL5-20P 3.0m (24)NEMA5-20R
AP7832
RackPDU,Metered,ZeroU,30A,
100V,(24)NEMA5-15R
Vertical 2.9kW 120V NEMAL5-30P 3.0m (24)NEMA5-20R
AP8841
RackPDU2G,Metered,ZeroU,
30A,208V,(36)C13&(6)C19
Vertical 5.0kW 208V NEMAL6-30P 3.0m
(36)IEC320C13
(6)IEC320C19
AP8853
RackPDU2G,Metered,ZeroU,
32A,230V,(36)C13&(6)C19
Vertical 7.4kW 230V
IEC30932A
2P+E
3.0m
(36)IEC320C13
(6)IEC320C19
AP8858
RackPDU2G,Metered,ZeroU,20A/
208V16A/230V,(18)C13&(2)C19
Vertical 3.3kW
100–
240V
IEC-320C20 Inlet
(18)IEC320C13
(2)IEC320C19
AP8865
RackPDU2G,Metered,ZeroU,8.6kW,
208V,(36)C13&(6)C19&(2)5-20R
Vertical 8.6kW 208V3Ph NEMAL21-30P 1.8m
(36)IEC320C13
(6)IEC320C19
(2)NEMA5-20R
AP8866
RackPDU2G,Metered,ZeroU,
17.2kW,208V,(6)C13&(12)C19
Vertical 17.3kW 208V3Ph
IEC30960A
3P+PE
1.8m
(6)IEC320C13
(12)IEC320C19
AP8868
RackPDU2G,Metered,ZeroU,
10.0kW,208V,(36)C13&(6)C19
Vertical 10.0kW 208V3Ph CS8365C 1.8m
(36)IEC320C13
(6)IEC320C19
AP8881
RackPDU2G,Metered,ZeroU,
11kW,(36)C13&(6)C19
Vertical 11kW 400V3Ph
IEC30916A
3P+N+PE
1.8m
(36)IEC320C13
(6)IEC320C19
AP8886
RackPDU2G,Metered,ZeroU,
22.0kW,(30)C13&(12)C19
Vertical 22kW 400V3Ph
IEC30932A
3P+N+PE
1.83m
(30)IEC320C13
(12)IEC320C19
Next Generation PDU Features (AP8000 series)
APC Exclusive Locking
IEC Connectors
New Interactive LCD
Display and Advanced
Remote Management
Environmental
Monitoring – Exc Sensor
(AP9335T or AP9335TH)
Industry’s First
Ultra-Low-Prole
Breakers
For assistance with selecting the correct Rack PDU, and to view the entire range, please visit:
www.dellups.com/select-PDU.asp
For More Information on Rack PDU and Rack PDU Selector