Technical DataACRD100 ACRD101 ACRD200 ACRD201ACRD500ACRD501ACRD502InRow® RDAir-Cooled/Fluid-Cooled - 50/60 HzDATA CENTER SOLUTIONSFor More Information

Seite 2

InRow RD Technical Data Manual4Standard FeaturesCabinetThe frame is constructed of 16 gauge formed steel for maximum strength. The cabinet is servicea

Seite 3 - Contents

5InRow RD Technical Data ManualOptional FeaturesCable Water DetectorA leak detection cable is placed on the floor or subfloor around all possi-ble lea

Seite 4

InRow RD Technical Data Manual6Microprocessor ControllerMicroprocessor Controller The microprocessor controller is standard on each unit. The controll

Seite 5

7InRow RD Technical Data ManualAlarmsThe microprocessor controller shall activate a visible and audible alarm in the following occurrences:All series:

Seite 6

InRow RD Technical Data Manual8InRow RD ModelsExterior components: ACRD100 and ACRD200 seriesRemovable rear doorAdjustable leveling feetSide panel

Seite 7 - Overview

9InRow RD Technical Data ManualInterior components (front): ACRD100 seriesElectrical control box 1 (retractable)CompressorElectrical control box 2

Seite 8 - Scalable for High Density

InRow RD Technical Data Manual10Interior components (rear): ACRD100 seriesFilter/dryerHot gas bypass valvePressure transducer (2 total, located beh

Seite 9 - Hot Aisle Containment System

11InRow RD Technical Data ManualInterior components (front): ACRD200 seriesElectrical control box 1 (retractable)CompressorElectrical control box 2

Seite 10 - Standard Features

InRow RD Technical Data Manual12Interior components (rear): ACRD200 seriesFilter/dryerElectrical control box 2Pressure transducer (2 total, located

Seite 11 - Optional Features

13InRow RD Technical Data ManualExterior components: ACRD500 seriesRemovable rear doorsCasters (all swiveling)Side panel lockDoor handle and lock

Seite 12 - Microprocessor Controller

American Power Conversion Legal DisclaimerThe information presented in this manual is not warranted by the American Power Conversion Corporation to be

Seite 13

InRow RD Technical Data Manual14Interior components (front): ACRD500 seriesCondensate drain panFan (2)Thermal expansion valveFan guard (2)Compres

Seite 14 - InRow RD Models

15InRow RD Technical Data ManualInterior components (rear): ACRD500 seriesTable 1: Evaporator coilShutoff valvesCondensate drain panAir filtersSi

Seite 15

InRow RD Technical Data Manual16Electrical panel: ACRD100 and ACRD200 seriesLeak detector portBuilding management system (BMS) RS-485 portRemote te

Seite 16

17InRow RD Technical Data ManualElectrical panel: ACRD500 seriesTransformersUser interface connectorsMain controller boardRelay boardGround lugM

Seite 17

InRow RD Technical Data Manual18User interface panel: ACRD500 seriesRack inlet temperature sensors 1, 2, 3A-Link INA-Link OUTNetwork portConsole

Seite 18

19InRow RD Technical Data ManualPerformance SpecificationsNet Cooling Capacity (Air and Glycol Cooled)Return Air Temperature SKU Total Capacity kW (BT

Seite 19

InRow RD Technical Data Manual20Net Cooling Capacity (Water Cooled)Return Air Temperature SKU Total Capacity kW (BTU/hr) Sensible Capacity kW (BTU/hr)

Seite 20

21InRow RD Technical Data ManualPerformance at Percentage of Fan SpeedACRD100 Series% Fan SpeedVoltage/Phase/HzL/S (SCFM)Unit Power in kWCondenser Fan

Seite 21 - Table 1:

InRow RD Technical Data Manual22ACRD200 Series% Fan SpeedVoltage/Phase/Hz L/S (SCFM) Unit Power in kWNet Sensible Capacity kW (BTU/h) SA Temp °C (°F)R

Seite 22

23InRow RD Technical Data ManualACRD500 Series% Fan Speed Voltage L/S (SCFM) Unit Power in kWCondenser Fan Power in kWNet Sensible Capacity kW (BTU/h)

Seite 23

ContentsInRow RD Technical Data ManualiOverview ... 1Scalable Solution for Crit

Seite 24

InRow RD Technical Data Manual24General DataGeneral Specifications - ACRD200 SeriesData Units Water Cooled Glycol Mixture CooledNominal flow rate ente

Seite 25 - Performance Specifications

25InRow RD Technical Data ManualAir CooledData SKU ValueAIR SYSTEM - FAN (Standard Filter Installed)Size - mm (in)ACRD100 200 (7.9)ACRD101 200 (7.9)AC

Seite 26

InRow RD Technical Data Manual26 Electrical DataAltitude Correction FactorsRoom Condition: 72 DB/50% RHAltitude (ft) 0 1000 2000 3000 4000 5000 6000 7

Seite 27 - ACRD100 Series

27InRow RD Technical Data ManualDimensional DataACRD100 and ACRD200 seriesDimensions are shown in mm (in).na2231b

Seite 28 - ACRD200 Series

InRow RD Technical Data Manual28ACRD500 seriesDimensions are shown in mm (in).na2465a

Seite 29 - ACRD500 Series

29InRow RD Technical Data ManualNetShelter SX to VX Height Adapter: ACRD100 and ACRD200 seriesNetShelter SX to VX Height Adapter: ACRD500 seriesNetShe

Seite 30 - General Data

InRow RD Technical Data Manual30Piping and Mechanical ConnectionsRefrigeration Piping Diagram (ACRD100 and ACRD500 series)Note: Shutoff valves shown n

Seite 31 - Air Cooled

31InRow RD Technical Data ManualWater cooled piping (ACRD200 series)Note: Bottom piping shown.InRow RDGate valveBalancing valveHose bib*Strainer,

Seite 32 - Sound Performance Data

InRow RD Technical Data Manual32Glycol cooled piping (ACRD200 series)Note: Bottom piping shown.Expansion tank*Hose bibs*Tank fill*Gate valves*Flu

Seite 33 - Dimensional Data

33InRow RD Technical Data ManualTop piping and power access locations (ACRD100 series and ACRD200 series)Dimensions are shown in mm (in).Low voltage

Seite 34 - ACRD500 series

InRow RD Technical Data ManualiiPerformance Specifications ... 19Net Cooling Capacity (Air and Glycol Cooled) .

Seite 35

InRow RD Technical Data Manual34Bottom piping and power access locations (ACRD100 series and ACRD200 series)Dimensions are shown in mm (in).Electrica

Seite 36

35InRow RD Technical Data ManualTop piping and power access locations (ACRD500 series)Dimensions are shown in mm (in).Refrigerant discharge lineRefr

Seite 37 - Note: Bottom piping shown

InRow RD Technical Data Manual36Bottom piping and power access locations (ACRD500 series)Dimensions are shown in mm (in).Refrigerant liquid lineRefr

Seite 38

37InRow RD Technical Data ManualOutdoor Heat ExchangersAir Cooled Condensers - Mechanical Data (ACRD100 Series)Air Cooled Condensers Mechanical Data (

Seite 39

InRow RD Technical Data Manual38Air Cooled Condensers - Electrical Data (ACRD100 Series)SKU Voltage Phase Frequency FLA MCA MOPACCD75214 208-240V 1 ph

Seite 40

39InRow RD Technical Data ManualACCD75201 and ACCD75204ACCD75202 and ACCD75205ACCD75203 and ACCD75206Dimensions are shown in mm (in). Conden

Seite 41

InRow RD Technical Data Manual40ACCD75207ACCD75208 and ACCD75209Condensers shown above have 16 mm (0.63 in) mounting holes on each of their lower legs

Seite 42

41InRow RD Technical Data ManualACCD75216, ACCD75218, and ACCD75220ACCD75217 and ACCD75219ACFC75210ACFC75255Dimensions are shown in mm (in).na2893ana2

Seite 43 - Outdoor Heat Exchangers

InRow RD Technical Data Manual42ACFC75256ACFC75257Dimensions are shown in mm (in).Air-cooled Condenser FeaturesAvailable in one to three fan configura

Seite 44

43InRow RD Technical Data ManualGuide SpecificationsPART 1 — GENERAL1.01 SUMMARYA. The environmental control system shall be designed specifically for

Seite 45 - ACCD75203 and ACCD75206

InRow RD Technical Data ManualiiiGuide Specifications ...43Guidelines for Installation . . . . . .

Seite 46 - ACCD75215

InRow RD Technical Data Manual443. All exterior panels and frame shall be powder coated for durability and attractive finish. Exterior frame and panel

Seite 47 - ACFC75255

45InRow RD Technical Data Manual3. Alarms: The microprocessor controller shall activate a visible and audible alarm in the occurrence of the following

Seite 48 - Air-cooled Condenser Features

InRow RD Technical Data Manual46F. Cooling Coil And Condensate Pan1. ACRD100 and ACRD200 series:a. The cooling coil shall use corrugated aluminum fin

Seite 49 - Guide Specifications

47InRow RD Technical Data ManualJ. Temperature Sensors1. Internal Temperature Sensors: Thermistor temperature sensors shall be mounted behind the fron

Seite 50 - 460-480V 60Hz 22

InRow RD Technical Data Manual48Guidelines for InstallationThe InRow RD provides reliable, accurate temperature control of computer rooms, laboratorie

Seite 52

6/2010990-3236D-001APC Worldwide Customer SupportCustomer support for this or any other APC product is available at no charge in any of the following

Seite 54 - Guidelines for Installation

1InRow RD Technical Data ManualOverviewThe modular, row-based computer room cooling system offers efficient, predictable, and economical cooling for a

Seite 55

InRow RD Technical Data Manual2Scalable Solution for Critical EnvironmentsInRow AdvantagesThe row-based solution improves energy efficiency and coolin

Seite 56 - 6/2010990-3236D-001

3InRow RD Technical Data ManualHot Aisle Containment System Modular ceiling tiles and doors can be used to enclose the hot aisle. This increases the d