31NetShelter SX Enclosure: Unpacking, Installation, and Customization
3. The 600-mm enclosures can be joined so that their centers are 24 in or 600 mm apart. Align the
enclosures to use the appropriate holes on the front and rear of the enclosures for the spacing you
need and secure the enclosures using one M5 x 12 flat-head screw per bracket.
4. If 600-mm enclosures are joined together on 24-in centers, there is a gap between them. APC
offers optional baying trim (AR7600) to cover the gap between the enclosures. The trim snaps
into place without tools and can be installed after the units are joined together and have
equipment installed in them.
Note: 600-mm and 750-mm enclosures join together without a gap when joined using
the inner-most set of holes on the joining brackets.
5. Reconnect the grounding wires, and reinstall the doors, if needed.
See “Installing the doors” on page 13.
To connect a NetShelter SX enclosure to a NetShelter VX or NetShelter VS enclosure, APC offers a
separate joining kit (AR7601 for enclosures with 600-mm centers or AR7602 for enclosures with 24-in
centers). When using the AR7601, the NetShelter SX enclosure will be inset by 33.2 mm (1.3 in) from
the VX or VS enclosure.