InRow Half-Rack RC Installation22
Electrical Connections
The following electrical connections are required in the field:
Feeds A and B
•A-Link
Network Management Card
Temperature sensor
Communication (building management system)
See the electrical schematic, located on the lid of the electrical box, for all electrical
connections.
All electrical connections must be in accordance with national and local codes.
See the InRow RC nameplate for voltage and current requirements.
A power disconnect is required to isolate each InRow RC for maintenance and service.
All low-voltage connections, including data and control connections, must be made with properly
insulated wires. The low-voltage connections must have 300-V minimum insulation.
Electrical Hazard: Potentially dangerous and lethal voltages exist within this InRow RC.
More than one disconnect switch may be required to energize or de-energize this equipment.
Observe all cautions and warnings. Failure to do so could result in serious injury or death.
Only qualified service and maintenance personnel should work on this equipment.
Warning: Use a voltmeter to ensure that power is turned off before making any
electrical connections.
Note: Single phase service is required. Electrical service must conform to national and local
electrical codes. The InRow RC is grounded through the power cord.