33InRow RP CW Installation
Description of user interface connectors
Item Description
Rack temperature sensors 1, 2, 3 Three temperature sensors which must be
installed on the cold aisle side of the server
racks. See “Rack temperature sensors” on
page 35.
A-Link IN In and out connections for A-Link. The
terminators supplied with the equipment
must be plugged into the first A-link port and
the final A-Link port for the system.
A-Link OUT
Network port
10/100 Base-T Network port. Connects the
equipment to the network; Status and Link
LEDs indicate network traffic.
• Status LED—blinks orange and green at
startup; indicates the status of the network
connection (solid green—IP address estab-
lished; blinking green—attempting to obtain
an IP address).
• Link LED—blinks to indicate network traf-
fic (green—operating at 10 mbps; orange—
operating at 100 mbps).
Console port RS-232 communication port used for local
service access to the equipment. Use
configuration cable (APC part number 940-
0103) to connect to this port.
Customer output, Normally Closed
(NC)
Customer-configurable output relay which
can be activated for all types of alarms or
critical alarms. The relay can be connected to
external equipment using 30 Vac/dc, 2 A.
Customer output, Common (COM)
Customer output, Normally Open (NO)
Supply GND Can be used for customer input and output
interface.
Supply 12 Vdc Can be used for customer input and output
interface. Current limit is 20 mA.
Supply 24 Vdc Can be used for customer input and output
interface. Current limit is 20 mA.
Remote shutdown+ Used for remote shutdown of the InRow RP.
Voltage is applied from the internal power
supply or by using an external power supply.
Remote shutdown- Ground connection point for remote
shutdown supply source.