APC AP9617 Bedienungsanleitung Seite 61

  • Herunterladen
  • Zu meinen Handbüchern hinzufügen
  • Drucken
  • Seite
    / 104
  • Inhaltsverzeichnis
  • FEHLERBEHEBUNG
  • LESEZEICHEN
  • Bewertet. / 5. Basierend auf Kundenbewertungen
Seitenansicht 60
®
USER’S GUIDE
network management card
59
8- Amp Hours (AHr) The battery amp-hour size, in amp-hours.
9- Compensation Method On enables and
Off disables battery temperature
compensation.
10- Comp Temp Coefficient
(mV/degC/cell)
The compensation temperature coefficient, in millivolts.
Minimum: – 4.99
Maximum: 0
11- High Knee Temperature
(mV/degC/cell)
The temperature (in Celsius) above which Float Voltage
no longer changes to compensate for increase in
temperature.
Minimum: 0
Maximum: 100.00
12- Low Knee Temperature
(mV/degC/cell)
The temperature (in Celsius) below which Float Voltage
no longer changes to compensate for decrease in
temperature.
Minimum: – 100.00
Maximum: 100.00
13- Accept Changes Use this option to save your changes.
Menu Item Description
Seitenansicht 60
1 2 ... 56 57 58 59 60 61 62 63 64 65 66 ... 103 104

Kommentare zu diesen Handbüchern

Keine Kommentare