InRoom Controller - Operating Instructions46
E6
5 10 14 20 24 °C
1K
T/°C
Control
The corresponding commands:
Display
Humidification
Dehumidification (Part 1)
The start humidity for dehumidification is
entered as a positive difference to the room
humidity setpoint.
The hysteresis for the dehumidification stop
is entered in the 2nd line.
To avoid a feedback circle of dehumidification
and cooling, you can adjust a stop temperatu
-
re, which is entered as a negative difference
to the air temperature setpoint.
With a fixed hysteresis of 1 Kelvin the dehu-
midification is switched on again, when the
room temperature rises.
Adjusting the water temperature limits for
the dehumidification refers to the possibility
of dehumidifying the air by the free cooling
coil with fan speed reduction.
➍➎
If the water temperature limits are exceeded,
the controller commutes to dehumidification
by compressor operation.
See a detailed description on the next
page.
Note:
The dehumidification fan speed is adjusted
in the Air/Fan-menu.
On/Off-control
Dehumidific.
ON
OFF
setpoint
%r.h.
min max GE-off
water temp.
Dehumidification range
Dehumidif. -Stop
Deh.
ON
OFF
The surrounded numbers refer to the corre
-
sponding passages in the descriptive text.
dehumi start 7.0
dehumi hys 7.0
dehumi stop 2.0
dehumi min 4
dehumi max 10