63InRoom Controller - Operating Instructions
➊
➋
➌
➍
➎
➏
O1
O3
➊
➋
➌
Service
The corresponding commands:
Times are entered in hours.
The numbered callouts refer to the corres
-
ponding passages in the descriptive text.
Display Humidification
Humidifier
Setting the parameter ACTIVE to 1 adds a
humidifier to the configuration. Setting this
parameter to 0 disables the humidifier. ➊
In the next line you determine the humidifier
type (1: humidifier with on/off control, 2: hu-
midifier with proportional control).
➋
With the parameter "D-OUT" you determine
a digital output for an on/off humidifier. ➌
With the parameter "A-OUT" you adjust the
analogous output of the proportional signal
for a humidifier.
➍
The digital input for the humidifier alarm can
be assigned by the "D-IN" parameter. ➎
The humidifier runtime can be set in the
last line. ➏
Dehumidification
Setting the parameter ACTIVE to 1 adds a
dehumidification valve to the configuration.
Setting this parameter to 0 disables the
dehumidification valve.
➊
With the parameter "D-OUT" you determine
a digital output for the dehumidification (sole
-
noid valve for partial evaporator cut-off). ➋
In the second line you can configure a hot-
gas bypass for the compressor by entering
a "1". ➌
When dehumidification with compressor
operation is requested, the hotgas bypass
is closed, because the maximum refrigerant
mass flow is needed for the effect of passing
under the dew point.
This is also valid for dehumidification by
compressor operation with fan speed re-
duction.
Configuration of a conductivity meter
by commands only.
humi 1 conf 0
humi 1 type 2
humi 1 dout 11
humi 1 aout 4
humi 1 alarm 7
humi 1 runtime 500
humi 1 confcon 1
dehumi confvalve 1
dehumi dout 12
dehumi confbypass 1