APC INROOM ACPSC3000 Betriebsanleitung Seite 52

  • Herunterladen
  • Zu meinen Handbüchern hinzufügen
  • Drucken
  • Seite
    / 106
  • Inhaltsverzeichnis
  • LESEZEICHEN
  • Bewertet. / 5. Basierend auf Kundenbewertungen
Seitenansicht 51
InRoom Controller - Operating Instructions52
D7
F7
a
a
a
C7
C6
Control
The corresponding commands:
Times are entered in seconds.
The numbered callouts refer to the corres-
ponding passages in the descriptive text.
Display Air
Louver
The pre-start serves to open the louver
before the fan operation starts. This way
a fan operation against a closed louver is
avoided.
Function
Sensor
In combination with these alarms a com-
mon alarm can be released. ➊➍
The alarm delay for the limit alarm and
for the sensor failure alarm is entered
in seconds.
The limit value alarms
can be assigned
to an alarm relay as the sensor failure
alarm
.
With the trim offset you can calibrate the
sensor with the help of a reference ther-
mometer.
Compare the display of the PHYSICAL
VALUE with the value of the reference
thermometer.
Unit alarms
Three parameters can be adjusted for the
fire alarm, the water alarm, and phase
failure.
Release of a common alarm (0/1)
a,
alarm delay a and alarm relay assign-
ment a (named priority).
If, instead of a temperature, the
expression "reset" is entered, the
sensor calibration is deleted.
louver 1 pretime 100 sensor 1 alarmprio 2
sensor 1 commonalarm 1
sensor 1 alarmdelay 7
sensor 1 alarmpriobr 3
sensor 1 commonalarmbr 1
sensor 1 alarmdelaybr 8
sensor 1 trim 22.3
fire commonalarm 1
water alarmdelay 7
phase alarmprio 8
Seitenansicht 51
1 2 ... 47 48 49 50 51 52 53 54 55 56 57 ... 105 106

Kommentare zu diesen Handbüchern

Keine Kommentare