InRoom Controller - Operating Instructions6
1 10 21 30 41 50
11 20 31 40 51 60
JP 2 3 4 5
JP 6
JP 1
JP 7
JP 9 JP 8
OK-LED
TX1-LED
RX1-LED
Error-LED
2. Hardware components
2.1 I/O controller
2.1.1 Board design
Jumper setting depending on sensor types
Jp n° Pos.1-2 Pos.2-3
Analogous input
AIN 1 2
4-20mA
0-10V
AIN 2 3
AIN 3 4
AIN 4 5
AIN 5 6 PT1000 PT100
Pin position
Service port
RS232
plug for EBUS
ext. board
Jumper for software download
Jp n° Pos. 1-2 Pos. 2-3
7 operation download
Termination jumper
Jp n° Function, when set
1 I/O-bus Port 1 termin. (Pos.1-2)
8 EBUS Port 2 termination
9 EBUS Port 3 termination
Jp 1 has to be set if the I/O controller represents
the first or last unit in the I/O bus.
Jp8 and Jp9 have to be set if no EBUS extension
board is present. On the contrary, they have to
be removed to enable the two extension RS485
busses on a plugged EBUS extension board.
green LEDs for red LEDs for
digital inputs 1-11 digital outputs 1-7
Onboard LEDs
The function of the digital inputs is displayed by
green LEDs:
ON: Voltage present
OFF: No voltage (alarm, failure)
The function of the digital outputs is displayed by
red LEDs:
ON: Relay active
OFF: Relay passive
The OK-LED displays the I²C-bus clock.
The TX1/RX1-LEDs indicate data traffic on the
I/O bus (port 1).
The Error-LED lights up at any time, when an alarm
has occurred.
DIP-switches
for bus ID
4 sockets
for
EDIOs/
EAIOs
Bus driver
Technical Data:
Voltage supply: 24(
+15%) VAC
Power consumption: 9.6 VA
Fuse: 2 A time-lag
Operating temp.: 5°C...40°C
Storage temp.: -30°C...60°C