Installation Manual
1
How to Avoid Equipment Damage
Disconnect power for Smart-UPS or expansion chassis
You do not need to turn off a Symmetra
®
or MGE
®
Galaxy
®
UPS to install the UPS
Network Management Card 2 (NMC).
Damage to the UPS or NMC can result if you do not remove all AC and
DC power from a Smart-UPS
®
, an Expansion Chassis, or a Triple
Expansion Chassis before you install the Network Management Card.
Smart-UPS.
1. Turn off the equipment that connects to the UPS.
2. Disconnect the UPS from its AC input source.
3. Press the OFF button on the UPS for approximately five seconds to turn off
the DC (battery) power.
Expansion chassis. Make sure that the Expansion Chassis or Triple Expansion
Chassis is disconnected from any power source:
1. Disconnect the chassis cable from the UPS.
2. If the chassis uses an AC adapter (AP9505), disconnect that adapter from
the chassis.