Installation Manual
5
Installation in a UPS
How to install the card for different UPS models
You can install the UPS Network Management Card (NMC) in a card slot in a
Smart-UPS, Symmetra UPS, Galaxy 300, Galaxy 3500, or Galaxy 7000.
You cannot install this NMC in a Symmetra PX 250 or Symmetra PX
500 UPS.
In a Symmetra UPS that uses more than one management product, you must install
the management products in the correct order for them to operate properly.
See “How to Install Multiple Management Cards” on page 21.
You do not need to turn off power to install a Symmetra UPS.
Step 1: Turn off power (Smart-UPS)
Damage to the UPS or the NMC can result if you do not remove all AC
and DC power from a Smart-UPS.
Step 2: Install the Network Management Card
The NMC is sensitive to static electricity. When handling the NMC,
touch only the end plate while using one or more of these electrostatic-
discharge devices (ESDs): wrist straps, heel straps, toe straps, or
conductive shoes.
For the location of the UPS card slot, see the UPS documentation.
1. Locate the UPS card slot.
2. Use the same screws that hold the slot cover in place to secure the NMC in
the UPS card slot.