Operation: Using the Display
InfraStruXure InRow RC—Operation and Maintenance 5
Start the cooling unit
Path: Main Menu > On/Standby
To start the cooling unit, select the On/Standby option on the main
menu and change the setting to On. The cooling unit will run according
to the configured settings.
Stop the cooling unit
Path: Main Menu > On/Standby
To put the cooling unit into Standby mode, select the On/Standby option on the main menu and change
the setting to Standby.
Factory default settings
All the InRow RC settings are controlled through the display interface on the front of the InRow RC. The
factory default temperature is set at 72°F (22.2°C).
The default PID coefficient values for the RC's Cool (Fan
Speed) PID are:
Gain (P) = 0.67
Rate (I) = 0.37
Deriv (D) = 0.26
Note
On/Standby only affects the local cooling unit. You
must set the On/Standby option for each cooling unit
in the cooling group.
On/Standby
View Alarms
Clear Alarms
View Event Log
na1641a
Clear Event Log
Configure Modbus
Set Date & Time
Set Password
Set Display Units
Configure Display
Configure Network
About InRow RC
Set Identification
Service Intervals
View Run Hours
Configure Unit
Configure Group
Set Group PID
View Group Status
View Unit Status
Set Group Setpoints
Set Unit Thresholds
Warning
The Standby option does not remove power from the cooling unit. The cooling unit
has two power sources. You must disconnect both Power A and Power B to remove
power from the cooling unit.