6 InfraStruXure InRow RC—Operation and Maintenance
Set Up General Configuration
The cooling group configuration options are set during the commissioning of the cooling units in the
cooling group.
Cooling unit configuration
Path: Main > Configure Unit > General
Use the General menu to set the following:
Capacity. Set the cooling capacity of the cooling unit:
• Select Automatic to have your cooling unit automatically
control its output under normal (default) conditions.
• Select Maximum to run your cooling unit at full capacity.
Use this setting when commissioning a unit connected to a
Cooling Distribution Unit to set up the proper coolant flow.
Start-up Delay. The delay begins when the cooling unit is started
and initialized. The cooling unit cannot begin operation until this
delay has expired. Use the start-up delay to restart equipment
sequentially in your room after a scheduled downtime.
Idle on Leak. Set the cooling unit to enter idle mode if a leak is
detected.
Power Source. Select A, B, or A&B to indicate the InRow RC power line plugged into the power
source.
Caution
Changing the settings incorrectly can cause malfunctions to your cooling unit. Only
qualified service personnel should make changes to these settings.
Note
Normal checks for cooling failures are disabled in
the Maximum mode.
On/Standby
View Alarms
Clear Alarms
View Event Log
na1638a
Clear Event Log
Configure Modbus
Set Date & Time
Set Password
Set Display Units
Configure Display
Configure Network
About InRow RC
Set Identification
Service Intervals
View Run Hours
Configure Unit
Configure Group
Set Group PID
View Group Status
View Unit Status
Set Group Setpoints
Set Unit Thresholds
Kommentare zu diesen Handbüchern