Operation: Respond to Alarms
22 InfraStruXure InRow RC—Operation and Maintenance
Alarm messages and suggested actions
Displayed Alarm Message Severity Action Required
Air Containment High Pressure
Fault
Warning • Make sure the sensor is connected properly.
• If the problem persists, replace the sensor, or contact
APC Worldwide Customer Support. Refer to the back
page of this manual for contact information.
Air Containment Pressure
Sensor Fault
Warning • A hardware failure exists, replace the sensor, or contact
APC Worldwide Customer Support. Refer to the back
page of this manual for contact information.
Air Filter Clogged Warning • Clean or replace the air filter.
• If the problem persists, replace the sensor, or contact
APC Worldwide Customer Support. Refer to the back
page of this manual for contact information.
Air Filter Run Hours Violation Warning • Reset the Air Filter Run Hours after the air filter is
cleaned or replaced.
A-Link Isolation Relay Fault Critical • A hardware failure exists. For assistance, if the problem
persists, replace the sensor, or contact APC Worldwide
Customer Support. Refer to the back page of this
manual for contact information.
Coil Fluid Valve Actuator Fault Critical • A hardware failure exists. For assistance, if the problem
persists, replace the sensor, or contact APC Worldwide
Customer Support. Refer to the back page of this
manual for contact information.
Condensate Pan Full Fault Critical • Make sure the floats are operating correctly.
• Clear debris from the condensate pan and drain lines.
• If the problem persists, replace the sensor, or contact
APC Worldwide Customer Support. Refer to the back
page of this manual for contact information.
Condensate Pump Fault Warning • Clear debris from the condensate pump reservoir and the
condensate removal lines.
• Make sure the condensate removal lines are free of
obstructions and the float switch moves freely.
• If the problem persists, replace the sensor, or contact
APC Worldwide Customer Support. Refer to the back
page of this manual for contact information.
Cooling Failure Critical • A hardware failure exists. If the problem persists,
replace the sensor, or contact APC Worldwide Customer
Support. Refer to the back page of this manual for
contact information.
Entering Fluid Temperature
High Violation
Warning • Make sure the chiller is operating properly.
Make sure the Inlet Fluid threshold is set correctly in the
“High Temp Threshlds” screen.
• If the problem persists, replace the sensor, or contact
APC Worldwide Customer Support. Refer to the back
page of this manual for contact information.