36 InfraStruXure InRow RC—Operation and Maintenance
How to Recover From a Lost Password
Use a local computer, a computer that connects to the InRow RC or other device through the serial
port, to access the control console.
1. Select a serial port at the local computer, and disable any service that uses that port.
2. Connect the APC modem cable (APC part number 940-0103) to the selected port on the
computer and to the serial port at the InRow RC (use the DB-9 connector on the back of the
electrical board).
3. Run a terminal program (such as HyperTerminal
®
) and configure the selected port as follows:
– 9600 bps
– 8 data bits
–no parity
–1 stop bit
– no flow control
4. Press the Reset button on the back of the electrical panel, immediately press
ENTER, repeatedly
if necessary, to display the User Name prompt.
Note
To access the serial port, remove the rear panel and lower air filter of the InRow RC.
Note
If you do not press the ENTER key before 5 seconds elapses, you must press the Reset
button again.
na2005a
DB-9 connector
Reset button