InfraStruXure InRow RC—Operation and Maintenance 17
Set Up Network Configuration
Configure the network settings for the Network Management Card from the display interface. The
management card allows remote control and configuration of the InRow RC.
Network configuration
Path: Main > Configure Network
MAC Address.
Displays the unique network identifier assigned to
each Network Management Card at the factory.
Path: Main > Configure Network > IP Address
You will be prompted to enter an Admin password. Enter the
password and press
ENTER to return to the IP Address screen. Press
ENTER again to change the following settings.
IP. Enter the IP address assigned to this cooling unit’s Network
Management Card (manual mode only).
SM. Enter the subnet mask for this cooling unit’s Network
Management Card (manual mode only).
GW. Enter the default gateway for this cooling unit’s Network Management Card (manual mode
only).
Path: Main > Configure Network > Boot Mode
Boot Mode.
Set the method by which the cooling unit’s Network Management Card will acquire its
network settings.
• Manual—Scroll down and enter the network settings for the cooling unit’s Network
Management Card.
• BOOTP—Set the Network Management Card to obtain its network settings from a BOOTP
server.
• DHCP—Set the Network Management Card to obtain its network settings from a DHCP server.
• BOOTPDHCP—Set the Network Management Card to search for its network settings from
either a BOOTP or a DHCP server.
On/Standby
View Alarms
Clear Alarms
View Event Log
na1640a
Clear Event Log
Configure Modbus
Set Date & Time
Set Password
Set Display Units
Configure Display
Configure Network
About InRow RC
Set Identification
Service Intervals
View Run Hours
Configure Unit
Configure Group
Set Group PID
View Group Status
View Unit Status
Set Group Setpoints
Set Unit Thresholds
MAC: 001125876910
IP Address
Boot Mode: Manual
na1649a
IP:159.214.087.075
SM:255.255.255.255
GW:159.214.086.001
na1648a