Operation: Respond to Alarms
InfraStruXure InRow RC—Operation and Maintenance 25
Rack Inlet High Temperature
Violation
Critical • Make sure the temperature sensor is connected and
placed properly.
• Make sure the Inlet Air threshold is set correctly in the
"High Temp Threshlds" screen.
• If the problem persists, replace the sensor, or contact
APC Worldwide Customer Support for assistance. Refer
to the back page of this manual for contact information.
Rack Inlet Temperature Sensor
Fault
Critical • Make sure the sensor is connected properly.
• If the problem persists, replace the sensor, or contact
APC Worldwide Customer Support for assistance. Refer
to the back page of this manual for contact information.
Return High Temperature
Violation
Warning • Make sure the temperature sensor is connected properly.
• Make sure the Return Air threshold is set correctly in the
"High Temp Threshlds" screen.
• If the problem persists, replace the sensor, or contact
APC Worldwide Customer Support. Refer to the back
page of this manual for contact information.
Supply Air High Temperature
Violation
Warning • Make sure the temperature sensor is connected properly.
• Make sure the Supply Air threshold is set correctly in
the "High Temp Threshlds" screen.
• If the problem persists, contact APC Worldwide
Customer Support. Refer to the back page of this
manual for contact information.
Displayed Alarm Message Severity Action Required
na1962a
Supply Air
Temperature
Sensor
Supply Air
Temperature
Sensor
Return Air
Temperature
Sensor
Return Air
Temperature
Sensor
Remote Air
Temperature
Sensor