USERS GUIDE
network management card
98
PowerChute Network Shutdown Parameters
Parameter Definition
Maximum Shutdown
Time
Defines the maximum time that the UPS at a PowerChute
Network Shutdown client waits before it shuts down in response
to a graceful turn-off command.
N
OTE: For information about this shutdown delay is
determined, see Maximum-Shutdown-Time negotiation.
Shutdown Behavior Defines how the UPS turns off after the PowerChute Network
Shutdown clients finish shutting down their computer systems.
Add Client IP
Address
Allows you to add as many as 50 PowerChute Network
Shutdown clients to the list Configured Client IP Addresses.
N
OTE: When you install a PowerChute Network Shutdown
client on your network, it is added to the list automatically.
Configured Client IP
Addresses
Allows you to view the list of PowerChute Network Shutdown
clients, and remove PowerChute Network Shutdown clients
from the list.
N
OTE: When you uninstall a PowerChute Network Shutdown
client, it is removed from the list automatically.