USER’S GUIDE
network management card
76
Status Field Definition
Load Current
1, 2
or
Output Current
3
The current, in Amps, supplied to the load.
Load Power
1, 2
The UPS load as a percentage of available Watts.
Apparent Load
Power
1, 2
The UPS load as a percentage of available VA.
Output Frequency
4
The frequency, in Hz, used by the output voltage. In the control
console for Smart-UPS or Matrix-UPS, the Operating Frequency
field reports the frequency value shared by the input and output
voltages.
Output kVA
5
or
Output Power
6
The load placed on each phase by the attached equipment, in total
kVA.
Output Power
Percentage
6
The load placed on each phase by the attached equipment,
expressed as a percentage of the available kVA.
Output VA at n+0
7
The load placed on each phase by the attached equipment, as a
percentage of the VA available with no redundancy.
Output VA at n+1
7
The load placed on each phase by the attached equipment, as a
percentage of the VA available with the identified redundancy.
Output Voltage The AC voltage the UPS is providing to its load.
Output Watts at n+0
7
The load placed on each phase by the attached equipment, as a
percentage of the Watts available with no redundancy.
Output Watts at n+1
7
The load placed on each phase by the attached equipment, as a
percentage of the Watts available with the identified redundancy.
Peak Output Current
8
The highest current, in Amps, output by each phase.
1Matrix-UPS
2 Smart-UPS
3 Symmetra, Symmetra PX UPS, or Silcon UPS
4 Smart-UPS, Matrix-UPS, or Symmetra UPS
5 Symmetra PX UPS
6 Silcon UPS
7 Symmetra or Symmetra PX UPS
8 Symmetra PX UPS or Silcon UPS