Action Definition
Turn UPS On
(control
console)
This action turns on power at the UPS.
For a Synchronized Control Group, after a delay of a few seconds, the
action turns on all enabled group members that have input power.
Turn UPS Off This action turns off power immediately at the UPS, without a shutdown
delay, and the UPS remains off until you turn on its power again.
If the UPS is a member of a Synchronized Control Group, this action
turns off power at all UPSs that are enabled members of the group. No
Shutdown Delay is used. The UPSs turn off after a few seconds, and
they remain off until you turn on their power again.
N
OTE: For a synchronized turn-off action that uses the Shutdown
Delay of the initiating UPS, use SNMP. Set the value
turnUpsSyncGroupOffAfterDelay (5) for the upsAdvControlUpsOff
OID.
Turn UPS Off
Gracefully
1
(control
console)
This action turns off power after the UPSs Maximum Shutdown Time
plus two minutes, and its Shutdown Delay. For information about how
the Maximum Shutdown Time is determined, see Maximum-
Shutdown-Time negotiation.
For a Synchronized Control Group, the action is performed using the
delays configured for the group member that initiated the action.
1 When you select Yes for the Web interface’s Signal servers option, initiating a Turn UPS
Off, Reboot UPS, or Put UPS To Sleep action is equivalent to selecting Turn UPS Off
Gracefully, Reboot UPS Gracefully, or Put UPS To Sleep Gracefully in the control
console.