USER’S GUIDE
network management card
90
Utility Line Settings
This Configuration menu option is available to all UPS models except a
Silcon UPS. The available settings differ based on the UPS model.
Smart-UPS or Matrix-UPS. Not all Utility Line settings are available for
all Smart-UPS and Matrix-UPS models, and each setting’s selections can
differ by UPS model.
Setting Definition
Output Voltage The nominal AC voltage level for the UPS output.
High Transfer
Voltage
The upper limit of acceptable input voltage. When the input
reaches this value:
• Matrix-UPS switches to battery operation
• Smart-UPS starts to use its AVR Trim feature.
Low Transfer Voltage The lower limit of acceptable input voltage. When the input
reaches this value, Smart-UPS starts to use its AVR Boost
feature or switches to battery operation if it does not have this
feature.
N
OTE: For Matrix-UPS, this setting cannot be changed.
Bypass Upper
Voltage
The input voltage above which the UPS cannot switch to bypass
mode.
Bypass Lower
Votage
The input voltage below which the UPS cannot switch to bypass
mode.
Vout Reporting
(Matrix-UPS)
How Matrix-UPS scales its output voltage readings.
Sensitivity How sensitive the UPS will be to distortions in the input voltage.
NOTE: Matrix-UPS always uses the Automatic setting.
Output Frequency
Range
Defines the nominal value for the frequency used by the output
voltage.